The 501/421 dual certified Exe/Exd cable gland is intended for use on non-armoured elastomer and plastic insulated cables. This cable gland may be used with braided cables where the braid and outer sheath pass into the enclosure. For Exd application the cable must be suitable inline with 60079-14. The braid must then be suitably terminated inside the enclosureSee technical section for installation rules and regulations.
Elastomeric Exd flameproof seal on cable inner sheath.
Rounded Cable entry to prevent cable damage.
Prensa Cabo Não Armado Ex 501/421/ 3/4 pol (N) NPT Size B
Technical Specification
Application: Suitable for use in Zone 1, Zone 2, Zone 21 and Zone 22.
Ingress Protection: IP66, IP67 and IP68 (30 metres for 7 days) to IEC/EN 60529 and NEMA 4X.
Material: Brass, NP Brass or Stainless Steel.
Operating Temperature: -60°C to +100 °C.
Series: Group II Cable Glands.
Measures:
Weight (kg): 0.2796
Thickness (cm): 3.6500
Width (cm): 3.6500
Length (cm): 5.6100